1. Bathroom Electrics
The modern UK standards and regulations for electrical wiring no longer differ substantially from those in other European countries, but differ significantly from other countries with
- ring circuits
- fused plugs
- switched sockets
- historic wiring colors
- asymmetric supply-voltage tolerances
2. Bathroom Zones
The installation of electrical devices in bathrooms and shower rooms is regulated in Section 601 of BS 7671, and Part B of the Building Regulations. For such rooms, four special zones are defined, in which additional protection is required for electrical facilities: Zone 0 is the smallest rectangular volume that contains the bathtub, shower basin, etc. Zone 1 is the area above Zone 0, up to a height of 2.25 m above the floor. Zone 2 is the area above Zone 1 up to a height of 3 m, as well as the area that is horizontally within 0.6 m from Zone 1. Zone 3 is the area above Zone 2 up to a height of 3 m, as well as the area that is horizontally within 2.4 m from Zone 2.
Within Zone 0, only Separated Extra Low Voltage devices are permitted. Any AC transformer supplying such a device must be located outside Zones 0-2. The minimum required ingress protection rating in Zone 0 is IPX7 and IPX4 in Zone 1 and 2. If water jets are likely to occur, at least IPX5 is required in Zone 1-3. Otherwise, in Zone 3 and beyond, an ingress protection rating of IP20 is the minimum required. Equipment in Zone 1-3 must be protected by a 30 mA residual-current circuit breaker (except for shower pumps and shower heaters, where the use of an RCD is so far only recommended). Shaving sockets (with isolating transformer) are permitted in Zone 2 if direct spray from a shower is unlikely, even if they are only IP20. In a bathroom or shower room, such shaving sockets are the only sockets permitted in the entire room. In any other room with a bathtub or shower, normal sockets are permitted as long as they are outside Zone 3.

